Transformer Sizing Calculator
Calculate total apparent power in volt-amperes (VA) and find the standard catalog transformer capacity for single-phase and three-phase loads.
Standard Transformer Ratings Table
How Transformer VA is Calculated
Apparent power represents the total volt-ampere demand on the supply:
Single-Phase: VA = Voltage × Current
Three-Phase: VA = Voltage × Current × √3 (≈ 1.732)
Worked Example
For a single-phase 240 V, 20 A circuit: VA = 240 × 20 = 4,800 VA (4.8 kVA). The next standard NEMA size is 5,000 VA (5 kVA). If sized for continuous duty (+25% margin): 4,800 × 1.25 = 6,000 VA, leading to a 7,500 VA (7.5 kVA) transformer.
Frequently Asked Questions
Should I size a transformer to match the exact calculated VA?
No. Industry best practice recommends adding a 20% to 25% safety margin for continuous duty and future expansion. Transformers operating at near 100% capacity continuously produce excess heat and experience shorter lifespans.
What is the difference between VA and Watts?
Watts measure real power consumed by resistive loads. Volt-Amperes (VA) measure apparent power including reactive current caused by inductors and capacitors (power factor). Transformer coils and wiring must be sized to carry total VA.